SECTION 078100 – APPLIED FIREPROOFING
SPRAYED FIRE-RESISTIVE MATERIALS
A. Standard Durability SFRM for Interior Locations, Concealed Conditions: Manufacturer’s standard, factory-mixed, lightweight, dry formulation, complying with indicated fire-resistance design, and mixed with water at project site to form a slurry or mortar before conveyance and application.
- Products: Subject to compliance with requirements, provide the following:
a. GCP Applied Technologies (formerly WR Grace); Monokote MK-6 Series
b. Dry mixed mineral fiber and/or slag wool products (i.e. CAFCO BLAZE-SHIELD II / ISOLATEK Type II) are not acceptable substitutes.
2. Bond Strength: Minimum 200 psf (9.58 kPa) cohesive and adhesive strength based on field testing according to ASTM E 736.
“Density” Subparagraph below corresponds to minimum density required by the 2006 IBC. The IBC 2007 Supplement requires not less than the density specified in the approved fire-resistance design. Verify required density with authorities having jurisdiction.
3. Density: Not less than 15 pcf (240 kg/cu. m) and as specified in the approved fire-resistance design, according to ASTM E 605.
4. Thickness: As required for fire-resistance design indicated, measured according to requirements of fire-resistance design or ASTM E 605, whichever is thicker, but not less than 0.375 inch (9 mm).
5. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
a. Flame-Spread Index: 0.
b. Smoke-Developed Index: 0.
6. Compressive Strength: Minimum 10 psi (68.9 kPa) according to ASTM E 761.
7. Corrosion Resistance: No evidence of corrosion according to ASTM E 937.
8. Deflection: No cracking, spalling, or delamination according to ASTM E 759.
9. Effect of Impact on Bonding: No cracking, spalling, or delamination according to ASTM E 760.
10. Air Erosion: Maximum weight loss of [0.0 g/sq. ft. (0. 0 g/sq. m)] in 24 hours according to ASTM E 859.
11. Fungal Resistance: Treat products with manufacturer’s standard antimicrobial formulation to result in no growth on specimens per ASTM G 21.
12. Finish: Spray-textured finish.
13. Global Warming Potential (GWP) : Maximum GWP (as defined in kg CO2 per 1000 kgs of product) shall be 210 kgs.